Abstract Connection of supply neutral to the open terminal of a Three Phase Induction Motor under single phasing condition produces the required phase difference between winding voltages and starting torque is developed. Neutral connection is used only for starting and not for running. Otherwise the current exceeds the rated value even at no-load.
The open conductor condition in any one phase of a Beta-phase supply may occur due to the burning of any one fuse/jumper connection, a loose contact in one conductor or any other reason. A Beta-phase induction motor, drawing power from a Beta-phase supply, continues to run under such a single phasing condition and delivers reduced ...